Brand: SHANGFANG

Model: SF-634

 

Features 
Temperature Display/ Temperature Control
Manual, automatic defrost by electric heater
Evap. Fan Control/ Value Storing
Time、temperature setting to end defrosting
Self Testing /Parameter Locking 

Technical Data 
Range of temperature displayed : —45~66℃ (-45~150℉)  
Range of set temperature: —45~45℃ (-45~120℉)  
Accuracy: ±1℃(±2℉)
Compressor:  N.O.16A/250VAC 
Defrost:          N.O.10A/250VAC
Evap. Fan:      N.O.  5A/250VAC
Dimension:77(Length)×35(Width)×60(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
 
Parameters 

Parameter
Function
Set range
Default
E1
Lower setpoint limit
-45℃/-45℉~Set temp.
-35℃/-31℉
E2
Higher setpoint limit
Set temp.~45℃/120℉
20℃/68℉
E3
Temp.Hysteresis
1~10℃/1~18℉
4℃/7℉
E4
Comp.start delay time
0~10Min
2Min
E5
Offset on room temp.
-20~20℃/-36~36℉
0
E6
Offset on evap.temp.
-20~20℃/-36~36℉
0
F1
Max.defrost duration
1~60Min
20Min
F2
Defrost interval time
0~24Hr
6Hr
F3
Defrost termination temp.
0~20℃/32~68℉
8℃/46℉
F4
Display during defrost
0=Normal display
1=Last value before defrost
0
F5
Fan operating function
0=Parallel with comp.
1=Continuous running except defrost
0
C1
Temperature unit
C=Celsius   F=Fahrenheit
C

 

SF-634 TEMPERATURE CONTROLLER

SKU: R009077
$160.00Price

    Address:​

    Unit 19/4A (Main Store) and Unit 27/4A

    Bachell Ave,

    Lidcombe  NSW 2141

    Call us 

    Tel: (02) 9749  5401
                   9749 9532

    Email us :

              info@haiton.com.au
              sales@haiton.com.au
              jeff@haiton.com.au
              lisa@haiton.com.au

     

    We Accept

    Trading Hour

              Mon - Fri 7:30 am -6:15 pm

              Sat 9:30 am -2:30 pm

     

    © 2023 by Copyright® 2011 Haiton International Pty Ltd, All rights reserved.