Technical Data
Range of temperature displayed : —45~66℃ (-45~150℉)
Range of set temperature: —45~45℃ (-45~120℉)
Accuracy: ±1℃(±2℉)
Compressor: N.O.16A/250VAC
Defrost: N.O.10A/250VAC
Evap. Fan: N.O. 5A/250VAC
Dimension:77(Length)×35(Width)×60(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Parameter | Function | Set range | Default |
E1 | Lower setpoint limit | -45℃/-45℉~Set temp. | -35℃/-31℉ |
E2 | Higher setpoint limit | Set temp.~45℃/120℉ | 20℃/68℉ |
E3 | Temp.Hysteresis | 1~10℃/1~18℉ | 4℃/7℉ |
E4 | Comp.start delay time | 0~10Min | 2Min |
E5 | Offset on room temp. | -20~20℃/-36~36℉ | 0 |
E6 | Offset on evap.temp. | -20~20℃/-36~36℉ | 0 |
F1 | Max.defrost duration | 1~60Min | 20Min |
F2 | Defrost interval time | 0~24Hr | 6Hr |
F3 | Defrost termination temp. | 0~20℃/32~68℉ | 8℃/46℉ |
F4 | Display during defrost | 0=Normal display 1=Last value before defrost | 0 |
F5 | Fan operating function | 0=Parallel with comp. 1=Continuous running except defrost | 0 |
C1 | Temperature unit | C=Celsius F=Fahrenheit | C |