Brand: Elitech
Model: SF-104
Features
Temperature control
Evaporator fan control
Automatic/manual defrost by electric heater
Time/temp. seting to end defrost
Re-start delay
Technical Data
Range of temperature displayed : —45~45℃ (-40~120℉)
Range of set temperature: —45~45℃ (-40~120℉)
Accuracy:±1℃ (±2℉)
Compressor: N.O. 20A/250VAC(one HP)
Defrost: N.O. 10A/250VAC
Evap. Fan: N.O. 5A/250VAC
Dimension:77(Length)×35(Width)×60(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Parameter | Function | Set range | Default |
E1 | Lower setpoint limit | -45℃/-45℉~Set temp. | -22℃/-8℉ |
E2 | Higher setpoint limit | Set temp.~45℃/120℉ | 20℃/68℉ |
E3 | Temp.Hysteresis | 1~10℃/1~18℉ | 4℃/7℉ |
E4 | Comp.start delay time | 0~10Min | 03Min |
E5 | Offset on room temp. | -20~20℃/-20~20℉ | 0 |
E6 | Offset on evap.temp. | -20~20℃/-20~20℉ | 0 |
C1 | Temperature unit | ℃=Celsius ℉=Fahrenheit | ℃ |
F1 | Max.defrost duration | 1~60Min | 20Min |
F2 | Defrost interval time | 0~24Hr | 04Hr |
F3 | Defrost termination temp. | 0~20℃/32~68℉ | 8℃/46℉ |
F4 | Display during defrost | 0=Normal display 1=Last value before defrost | 0 |
F5 | Fan operating function | 0=Parallel with comp. 1=Continuous running except defrost | 0 |