Brand: SHANGFANG

Model: SF-104S

 

Features 
Temperature control
Evaporator fan control
Automatic/manual defrost by electric heater
Time/temp. seting to end defrost
Celsius/Fahrenheit degrees
Re-start delay 

Technical Data 
Range of temperature displayed :  -45~45℃(-40~120℉)
Range of set temperature: -45~45℃ (-40~120℉)
Accuracy:±1℃ (±2℉)
Compressor: N.O. 30A/250VAC
Defrost: N.O. 30A/250VAC
Evap. Fan: N.O. 30A/250VAC
Dimension:77(Length)×35(Width)×30(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm

Parameters 

Parameter
Function
Set range
Default
E1
Lower setpoint limit
-45℃/-45℉~Set temp.
-22℃/-8℉
E2
Higher setpoint limit
Set temp.~45℃/120℉
20℃/68℉
E3
Temp.Hysteresis
1~10℃/1~18℉
4℃/7℉
E4
Comp.start delay time
0~10Min
03Min
E5
Offset on room temp.
-20~20℃/-20~20℉
0
E6
Offset on evap.temp.
-20~20℃/-20~20℉
0
C1
Temperature unit
℃=Celsius ℉=Fahrenheit
F1
Max.defrost duration
1~60Min
20Min
F2
Defrost interval time
0~24Hr
04Hr
F3
Defrost termination temp.
0~20℃/32~68℉
8℃/46℉
F4
Display during defrost
0=Normal display
1=Last value before defrost
0
F5
Fan operating function
0=Parallel with comp.
1=Continuous running except defrost
0

SF-104S TEMPERATURE CONTROLLER

SKU: R009063
$148.00Price

    Address:​

    Unit 19/4A (Main Store) and Unit 27/4A

    Bachell Ave,

    Lidcombe  NSW 2141

    Call us 

    Tel: (02) 9749  5401
                   9749 9532

    Email us :

              info@haiton.com.au
              sales@haiton.com.au
              jeff@haiton.com.au
              lisa@haiton.com.au

     

    We Accept

    Trading Hour

              Mon - Fri 7:30 am -6:15 pm

              Sat 9:30 am -2:30 pm

     

    © 2023 by Copyright® 2011 Haiton International Pty Ltd, All rights reserved.