Brand: SHANGFANG
Model: SF-124
Features
Temperature Control / Light Control
Manual,automatic defrost by turning off
Condenser high temperature alarm
Value Storing / Self Testing
Parameter Locking
Technical Data
Range of temperature displayed : —45~150℃
Range of set temperature: —45~80℃
Accuracy:±1℃
Compressor: N.O. 20A/240VAC
Defrost: N.O. 10A/240VAC
Light : N.O. 5A/240VAC
Dimension:77(Length)×35(Width)×60(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Parameter | Function | Set range | Defrost |
E1 | Lower setpoint limit | -45℃~Set temp. | -35℃ |
E2 | Higher setpoint limit | Set temp.~80℃ | 30℃ |
E3 | Temp.hysteresis | 1~20℃ | 4℃ |
E4 | Comp.start delay time | 0~10Min | 2Min |
E5 | Offset on room temp. | -20~20℃ | 0 |
E6 | Offset on condenser sensor | -20~20℃ | 0 |
F1 | Max.defrost duration | 1~60Min | 20Min |
F2 | Defrost interval time | 0~24Hr | 6Hr |
F4 | Display during defrost | 0=Nomal display 1=Last value before defrost | 0 |
C2 | Condenser high temp. alarm value | 0~120℃ | 80℃ |
C4 | Alarm time delay | 0~90Min | 30Min |