Features 

Mini-sized and integrated temperature control

can directly control 1HP compressor (include 1HP)

Temperature display/Temperature control

Manual, automatically defrost/

Evap. fan control/ Time, temperature setting to end defrost

Energy saving mode/

Light control/Value storing

Parameter locking/ Self testing

 

Technical Data 

Temperature display range: -45~66℃(-45~150℉)

Set temperature range:-40℃~45℃(-40~113℉)

Accuracy:±1℃(1℉)        

Temperature sensor: NTC, two sensors, 2 meters (Neither positive nor negative ,white)

Compressor :N.O. 30A/250VAC (can directly connect to 1HP compressor, if more needs

to connect an AC contactor)

Defrost heater: N.O. 8A/250VAC (can directly connect to 1KWload, if more needs to

connect an AC contactor)

Evap. fan: N.O.5A/250VAC Lihgt: N.O.5A/250VAC

Increase dor (condenser sensor, door switch, alarminput) model

Dimension:77 L mm 35(W)mm 70(D)mm

Mounting hole dimension: 71mm L 29mm(W)


Parameters 

 

 

Paramete

Function

Set range

Default

PAS

Password

0 0~99

1 5

E1

Lowest set point limit

-40℃/-40℉~Set temp.

-25℃/-13℉

E2

Higher set point limit

Set temp.~46℃/113℉

20℃/68℉

E3

hysteresis

01~20℃/02~36℉

04℃/07℉

E40

Comp.start delay time 

00~10Min

2Min

E41

Delay starting time

00~10Min

2Min

E5

Offset on room temp.

-20~20℃/-36~36℉

00℃/00℉

E6

Offset on evap. Temp

-20~20℃/-36~36℉

00℃/00℉

E7

Offset on condenser temp.

-20~20℃/-36~36℉

00℃/00℉

F0

Defrost type

00=defrost by turning off comp.

01=heating defrost

02=hot gas defrost

01

FF0

when enter hot gas defrost comp. delay starting time

00~20Min

00Min

FF1

Defrost interval way

00=power on time

01=comp. continuously working time

00

F1

Max defrost duration

01~60min

20min

F2

Defrost interval

00~24Hr

6Hr

F30

Defrost starting

temperature

-40℃/-40℉~F31

00℃/32℉

F31

Defrost termination temperature

F30~40℃/104℉

08℃/46℉

F4

Display during defrost

00= normal display

01= last value before defrost

02=dEF

 

00

F5

Dripping time

00~30min

2min

P1

Fan control during refrigeration

00=synchronized with compressor

01= keep running

02=determined by P4, P5

00

 

SF-406 TEMPERATURE CONTROLLER

SKU: R009068
$158.00 Regular Price
$134.30Sale Price

Temp Controller LT

    Haiton International Pty Ltd/ Haiton Air Con & Refrigeration Pty Ltd

    LIDCOMBE (FLAGSTORE)

    Unit 19, 27, 31

    4A Bachell Avenue

    Lidcombe NSW 2141

    -

    (02) 9749 9532 / 9749 5401

    0425 470 512 / 0420 326 188

    -

    MON - FRI: 8am - 5pm

               SAT: 9am - 2pm

    KINGSGROVE BRANCH

    108/2 The Crescent, 
    Kingsgrove NSW 2208 

    -

    (02) 8384 9715

    0452 351 833

    -

    MON - FRI: 8am - 5pm
               SAT: CLOSED

    SMITHFIELD BRANCH

    5/189 McCredie Rd, 
    Smithfield NSW 2164 

    -

    (02) 8773 4301

    0420 326 188

    -

    MON - FRI: 8am - 4.45pm
               SAT: CLOSED

    © 2024 ® 2011 Haiton International Pty Ltd. All rights reserved.

    bottom of page