top of page

Brand: SHANGFANG

Model: SF-405

 

 

 

Features 

Mini-sized and integrated temperature control

can directly control 1HP compressor (include 1HP)

Temperature display/Temperature control/Manual

automatically defrost

Evap. fan control

Time, temperature setting to end defrost

Energy saving mode

Value storing/ Parameter locking

Self testing                  

 

Technical Data 

Temperature display range: -45~66℃(-45~150℉)

Set temperature range:-40℃~45℃(-40~113℉)

Accuracy:±01℃(02℉)        

Temperature sensor: NTC, three sensors (cold room& defrost control), 2 meters (Neither positive nor negative) Condenser sensor, door switch (optional)

Compressor :N.O. 30A/250VAC (can directly connect to 1HP compressor, if more needs

to connect an AC contactor)

Defrost heater: N.O. 8A/250VAC (can directly connect to 1KWload, if more needs to

connect an AC contactor)

Evap. fan: N.O.5A/250VAC Alarm: N.O.5A/250VAC

Increase dor (condenser sensor, door switch, alarminput) model selection input, when

door control input there is energy saving mode.

Dimension:77(L)mm×35(W)mm×70(D)mm

Mounting hole dimension: 71mm( L)×29mm(W)


Parameters 

 

 

Paramete

Function

Set range

Default

PAS

Password

0 0~99

1 5

E1

Lowest set point limit

-40℃/-40℉~Set temp.

-25℃/-13℉

E2

Higher set point limit

Set temp.~45℃/113℉

20℃/68℉

E3

hysteresis

01~20℃/02~36℉

04℃/07℉

E40

Comp.start delay time 

00~10Min

2Min

E41

Delay starting time

00~10Min

2Min

E5

Offset on room temp.

-20~20℃/-36~36℉

00℃/00℉

E6

Offset on evap. Temp

-20~20℃/-36~36℉

00℃/00℉

E7

Offset on condenser temp.

-20~20℃/-36~36℉

00℃/00℉

F0

Defrost type

00=defrost by turning off comp.

01=heating defrost

02=hot gas defrost

01

FF0

when enter hot gas defrost comp. delay starting time

00~20Min

00Min

FF1

Defrost interval way

00=power on time

01=comp. continuously working time

00

F1

Max defrost duration

01~60min

20min

F2

Defrost interval

00~24Hr

6Hr

F30

Defrost starting

temperature

-40℃/-40℉~F31

00℃/32℉

F31

Defrost termination temperature

F30~40℃/104℉

08℃/46℉

F4

Display during defrost

00= normal display

01= last value before defrost

02=dEF

 

00

F5

Dripping time

00~30min

2min

P1

Fan control during refrigeration

00=synchronized with compressor

01= keep running

02=determined by P4, P5

00

SF-405 TEMPERATURE CONTROLLER

SKU: R026036
$195.00 Regular Price
$165.75Sale Price

Temp Controller LT

Quantity

    Haiton International Pty Ltd / Haiton Air Con & Refrigeration Pty Ltd

    LIDCOMBE (FLAGSTORE)

    Unit 19, 27, 31

    4A Bachell Avenue

    Lidcombe NSW 2141

    -

    (02) 9749 9532 / 9749 5401

    0425 470 512 / 0420 326 188

    -

    MON - FRI: 8am - 5pm

    SAT: 9am - 2pm

    KINGSGROVE BRANCH

    108/2 The Crescent, 
    Kingsgrove NSW 2208 

    -

    (02) 8384 9715

    0452 351 833

    -

    MON - FRI: 8am - 4:30pm
    SAT: Closed

    SMITHFIELD BRANCH

    5/189 McCredie Rd, 
    Smithfield NSW 2164 

    -

    (02) 8773 4301

    0420 326 188

    -

    MON - FRI: 8am - 4.45pm

    SAT: Closed

    Direct air conditioning importer, we provide parts and air conditioner installation for reverse cycle air conditioner, split system air conditioning, reverse cycle air con, ducted air conditioner. Best prices in Fujitsu split system, Panasonic aircon, Mitsubishi electric split system

    © 2024 ® 2011 Haiton International Pty Ltd. All rights reserved.