Brand: SHANGFANG
Model: SF-401
Features
Mini-sized and integrated temperature control, can directly control 1HP compressor (include 1HP)
Temperature display/Temperature control/Manual, automatically defrost/Value storing/
Parameter locking/Self testing
Technical Data
Temperature display range: -45~66℃(-45~150℉)
Set temperature range:-40℃~45℃(-40~113℉)
Accuracy:±01℃(02℉)
Temperature sensor: NTC, one sensor, 2 meters (Neither positive nor negative)
Compressor :N.O. 30A/250VAC (can directly connect to 1HP compressor, if more needs
to connect an AC contactor)
Alarm: N.O.5A/250VAC
Input signals door switch, alarm input (selectable), when door switch input there is energy saving mode.
Dimension:77 L mm 35(W)mm 70(D)mm
Mounting hole dimension: 71mm L 29mm(W)
Parameters
Paramete | Function | Set range | Default |
PAS | Password | 0 0~99 | 1 5 |
E1 | Lowest set point limit | -40℃/-40℉~Set temp. | -25℃/-13℉ |
E2 | Higher set point limit | Set temp.~45℃/113℉ | 20℃/68℉ |
E3 | hysteresis | 01~20℃/02~36℉ | 04℃/07℉ |
E40 | Comp.start delay time | 00~10Min | 2Min |
E41 | Delay starting time | 00~10Min | 2Min |
E5 | Offset on room temp. | -20~20℃/-36~36℉ | 00℃/00℉ |
FF1 | Defrost interval way | 00=power on time 01=comp. continuously working time | 00 |
F1 | Max defrost duration | 01~60min | 20min |
F2 | Defrost interval time | 00~24Hr | 6Hr |
F4 | Display during defrost | 00= normal display 01= last value before defrost 02=dEF
| 00 |
C1 | Cold room high temp. alarm | C2~45℃/113℉ | 40℃/104℉ |
C2 | Cold room lowtemp. alarm | 40℃/40℉~C1 | -40℃/-40℉ |
C4 | Alarmhysteresis | 01~20℃/02~36℉ | 02℃/04℉ |
C5 | Outer alarminput effective work way | 00= comp. stop running 01= running as C7, C8
| 00 |
C6 | Alarmafter delay | 00~99min | 2min |
C7 | Comp. force stop time | 01~99min | 10min |
C8 | Comp. force running time | 00= comp. stop running 01~99 = min starting time | 30min |
C9 | Alarmoutput type | 00= contact actuation when alarm 01= contact disconnect when alarm | 00 |
CF | Temperature unit | 00=℃/ Celsius 01=℉/Fahrenheit | 00 |