Digital thermsotat for kitchen model SF-108
Features
1 Temperature sensor:NTC,3pcs
2 Temperature control/Evap.Fan control
3 Manual/Automatic defrost by electric herater/hot gas
4 Time/Temp.setting to end defrost
5 High/Low temperature alarm
6 Condenser high temperature alarm
7 Value storing/Self testing
8 Mini-sized and integrated intelligent controller
9 Applicable to the compressor of 1HP
Technical Data
1 Range of temperature displayed:-45°C~150°C(-45°F~302°F)
2 Range of set temperature:-45°C~100°C(-45°F~212°F)
Accuracy:±1°C(±2°F)
3 Compressor:NO.30A/250VAC
Defrost:NO.10A/250VAC
Evap.Fan:NO.5A/250VAC
Output of the outside sealed transformer:12VAC
4 Temperature of the operating environment:-10°C~60°C(14°F~140°F)
Relative humidity:20%~90%(Non-condensing)
Size
Dimension:77(L)x35(W)x60(D)mm
Mounting hole dimension:71(L)x29(W)mm
Circuit diagram
Parameter
Parameter | Function | Set range | Default |
E1 | Lower setpoit limit | -45°C/-45°F~Set temp. | -35°C/-31°F |
E2 | Higher setpoint limit | Set temp.~100°C/212°F | 20°C/68°F |
E3 | Temp.hysteresis | 1~20°C/1~36°F | 4°C/7°F |
E4 | Comp.start delay time | 0~10Min | 2Min |
E5 | Offset on room temp. | -20~20°C/-36~36°F | 0 |
E6 | Offset on evap.temp. | -20~20°C /-36~36°F | 0 |
E7 | Offset on condens. | -20~20°C/-36~36°F | 0 |
F0 | Defrost function | 0=Electric heater 1=Hot gas | 0 |
F1 | Max.defrost duration | 1~60Min | 20Min |
F2 | Defrost interval time | 0~24Hr | 4Hr |
F3 | Defrost termination temp. | 0~30°C/32~86°F | 8°C/46°F |
F4 | Display during defrost | 0=Normal disply 1=Last value before defrost | 0 |
F5 | Fan operation function | 0=Parallel with comp. 1=Continuous running except defrost | 0 |
C1 | Temperature unit | °C=Celsius °F=Fahrenheit | °C |
C2 | High temperature alarm | C3~100°C/212°F | 40°C/104°F |
C3 | Low temperatur alarm | -45°C/-45~C2°F | -40°C/-40°F |
C4 | Alarm delay time | 1~90Min | 60Min |
C5 | Condenser temperature alarm value | 0~120°C/0~248°F | 80°C~176°F |