Brand: SHANGFANG
Model: SF-104P
Features
Temperature control
Manual/automaticdefrost by electric heater
Evap. Fan Control
Value Storing
Self Testing /Parameter Locking
Technical Data
Range of temperature displayed : -45~150℃(-40~150℉)
Range of set temperature: -45~45℃(-40~120℉)
Accuracy:±1℃(±2℉)
Compressor: N.O. 30A/250VAC
Defrost: N.O. 10A/250VAC
Evap. Fan: N.O. 5A/250VAC
Dimension:77(Length)×35(Width)×70(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Parameter | Function | Set range | Default |
PA | Password | 00~99 |
|
E1 | Lower setpoint limit | -45℃/-45℉~Set temp. | -22℃/-8℉ |
E2 | Higher setpoint limit | Set temp.~45℃/120℉ | 10℃/50℉ |
E3 | Temp.Hysteresis | 1~20℃/1~36℉ | 5℃/9℉ |
E4 | Comp.start delay time | 0~10Min | 2Min |
E5 | Offset on room temp. | -20~20℃/℉ | 0 |
E6 | Offset on evap.temp. | -20~20℃/℉ | 0 |
F1 | Max.defrost duration | 1~60Min | 20Min |
F2 | Defrost interval time | 0~24Hr | 4Hr |
F3 | Defrost termination temp. | 0~30℃/32~68℉ | 12℃/54℉ |
F4 | Display during defrost | 0=Normal display | 1 |
F5 | Fan operating function | 0=Parallel with comp. 1 = Continuous running except defrost 2= Evaporator temper-ature control | 0 |
F6 | Dripping time | 0~10 Min | 2Min |
F7 | Fan delay start mode after defrost | 0=time 1=Controlled by F9 | 1 |
F8 | Fan delay start time after defrost. | 0~10Min | 2 |
F9 | Fan start temp. (Defrost sensor temp.) | -30~30℃ -22~86℉ | -4℃ 25℉ |
C1 | Temperature unit | Celsius=℃Fahr.= ℉ | ℃ |
C2 | High temperature alarm | Set value~49℃/121℉~OFF | 40℃ 104℉ |
C3 | Low temperature alarm | OFF~~44℃/44℉~Set value | OFF |
C4 | Alarm time delay | 0~90Min | 30Min |